4-8 Programming & Operation MN722
Program Mode Continued
Reset Parameters to Factory Settings
Sometimes it is necessary to restore the parameter values to the factory settings. Follow
this procedure to do so. Be sure to change the Level 2 Motor Data block “Motor Rated
Amps” to the correct value after this procedure (restored factory setting is 999).
Note: All specific application parameters already programmed will be lost when
resetting the control to factory settings.
Note: After factory settings are restored, the drive must be re-tuned.
Action
Description Display Comments
Apply Power Keypad Display shows this
opening message.
Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation.
Display mode. Stop LED on.
Press PROG key Enter program mode.
Press or key
Scroll to Level 2 Blocks.
Press ENTER key Select Level 2 Blocks.
Press or key
Scroll to the Miscellaneous block.
Press ENTER key Select Miscellaneous block.
Press key
Scroll to Factory Settings
parameter.
Press ENTER key Access Factory Settings
parameter.
represents blinking cursor.
Press key
Scroll to YES, to choose original
factory settings.
Press ENTER key Restores factory settings. “Loading Presets” is first message
“Operation Done” is next
“No” is displayed last.
Press key
Scroll to menu exit.
Press ENTER key Return to Level 1 blocks. Exit Level 2 blocks.
Press or key
Scroll to Programming exit. Exit Programming mode and
return to Display mode.
Press ENTER key Return to display mode. Display mode. Stop LED on.